SPECIFICATION FOR STANDARD AMF PANEL 62.5 KVA

Cubicle type, base mounting control panel with hinged doors, undrilled bottom gland plate, AL. Bus Bar and accommodating the following:

SWITCH GEARS:

  • • 100A, 4 Pole Contactor for ALTERNATOR with Thermal O/L relay
  • • 100A, 4 Pole Contactor for MAINS (OPTIONAL)

BACK-UP PROTECTION:
MCCB for short circuit protection

MICROPROCESSOR BASED AMF MODULE INCORPORATING:

Functions:
Supply Failure Timer
Restoration Timer
3 Impulse automatic engine Start / Stop logic
Mains / Generator Voltage & Frequency Sensing

Multifunction Meter & PCC 0301 with Scrolling Readings for

  • • Water Temperature/ Lube Oil Pressure
  • • Voltage / Ampere/ Frequency / kW / kVA
  • • Running-hour counter

Fault Indication (LED Type)

  • • Over / Under Speed
  • • Fails To Start
  • • Low Oil pressure
  • • Battery Charger Failure
  • • High Engine Temperature

Electronic kWH meter (Counter Display)

Current Transformers

Indications (LED):
DG ON, Load on DG
Mains ON, Load on Mains, Battery Charger ON

Push Buttons (AMF MODULE BY PASS MODE)

  • • Engine START / STOP ( Provided on Engine Controller )
  • • Generator Contactor CLOSE / TRIP
  • • Mains Contactor CLOSE / TRIP (If provided)
  • • Fault ACCEPT / RESET

BATTERY CHARGER:
SMPS Based Unit with inbuilt Auto/Manual & Float/Boost Facility
DC Voltmeter & Ammeter (Separate)

PLHO / 0712/RKS/ASN