SPECIFICATION FOR STANDARD AMF PANEL 500 KVA

Cubicle type, base mounting control panel with hinged doors, undrilled bottom gland plate, AL. Bus Bar and accommodating the following:

SWITCH GEARS:

  • • 800A, 3 Pole ACB EDO Type with 140A,3P neutral contactor for ALTERNATOR
  • • 800A, 3 Pole ACB EDO Type with 140A,3P neutral contactor for MAINS (OPTIONAL)

MICROPROCESSOR BASED AMF MODULE INCORPORATING:

Functions:
Supply Failure Timer
Restoration Timer
3 Impulse automatic engine Start / Stop logic & engine fails to start lockout
Mains / Generator Voltage & Frequency Sensing.

ADDITIONAL FEATURES:

Metering:
Combined Meter for Voltage / Ampere / Frequency
Combined Meter for KW / Power Factor / KVA
Electronic kWH Meter (Counter Display)
Current Transformers

Relay:
Earth Fault Relay (Electronic type)

Indications (LED):
DG ON , Load on DG
Mains ON, Load on Mains, Battery Charger ON

Push Buttons (AMF MODULE BY PASS MODE):
Engine START / STOP
Generator Breaker CLOSE / TRIP
Mains Breaker CLOSE / TRIP ( if provided )
Fault ACCEPT / RESET

BATTERY CHARGER:
SMPS Based Unit with inbuilt Auto/Manual & Float/Boost Facility
DC Voltmeter & Ammeter (Separate)

PLHO / 0712/RKS/ASN